Data records
Each statement in Circuit Breaker Reference is recorded as a data record with its source, verification date, review status and history. The index lists 70 records by subject.
Test methods
Bolted connection resistance
| Record | Statement |
|---|---|
| tests.bolted-connection-resistance.equipment.breaker.acceptance | Bolted Connection Resistance is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.B.1 of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
| tests.bolted-connection-resistance.equipment.breaker.maintenance | Bolted Connection Resistance is specified for oil and vacuum automatic circuit reclosers in maintenance testing at clause 7.24.1.B.1 of ANSI/NETA MTS-2023. Value: oil and vacuum automatic circuit reclosers. |
Bushing power factor and capacitance
| Record | Statement |
|---|---|
| tests.bushing-power-factor-and-capacitance.equipment.breaker.acceptance | Bushing Power Factor and Capacitance is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.B.8 of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
| tests.bushing-power-factor-and-capacitance.equipment.breaker.maintenance | Bushing Power Factor and Capacitance is specified for oil and vacuum automatic circuit reclosers in maintenance testing at clause 7.24.1.B.8 of ANSI/NETA MTS-2023. Value: oil and vacuum automatic circuit reclosers. |
Circuit Breaker Timing and Travel
| Record | Statement |
|---|---|
| tests.circuit-breaker-timing-and-travel.equipment.ats-transfer.acceptance | Circuit Breaker Timing and Travel is specified for automatic transfer switches in emergency systems in acceptance testing at clause 7.22.3.B.8 of ANSI/NETA ATS-2025. Value: automatic transfer switches in emergency systems. |
| tests.circuit-breaker-timing-and-travel.equipment.ats-transfer.maintenance | Circuit Breaker Timing and Travel is specified for automatic transfer switches in emergency systems in maintenance testing at clause 7.22.3.B.7 of ANSI/NETA MTS-2023. Value: automatic transfer switches in emergency systems. |
| tests.circuit-breaker-timing-and-travel.equipment.breaker.acceptance | Circuit Breaker Timing and Travel is specified for medium-voltage vacuum circuit breakers in acceptance testing at clause 7.6.3.A.7, 7.6.3.A.12 of ANSI/NETA ATS-2025. Value: medium-voltage vacuum circuit breakers. |
| tests.circuit-breaker-timing-and-travel.governed-by.ansi-neta-ats | Circuit Breaker Timing and Travel is addressed in ANSI/NETA ATS-2025. |
| tests.circuit-breaker-timing-and-travel.governed-by.ansi-neta-mts | Circuit Breaker Timing and Travel is addressed in ANSI/NETA MTS-2023. |
| tests.circuit-breaker-timing-and-travel.title | The test method is named Circuit Breaker Timing and Travel. Value: Circuit Breaker Timing and Travel. |
Contact resistance
| Record | Statement |
|---|---|
| tests.contact-resistance.equipment.breaker.acceptance | Contact Resistance is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.B.3 of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
| tests.contact-resistance.equipment.breaker.maintenance | Contact Resistance is specified for oil and vacuum automatic circuit reclosers in maintenance testing at clause 7.24.1.B.3 of ANSI/NETA MTS-2023. Value: oil and vacuum automatic circuit reclosers. |
Control and functional verification
| Record | Statement |
|---|---|
| tests.control-and-functional-verification.equipment.breaker.acceptance | Control and Functional Verification is specified for low-voltage insulated-case circuit breakers in acceptance testing at clause 7.6.1.1.2.B.8 of ANSI/NETA ATS-2025. Value: low-voltage insulated-case circuit breakers. |
| tests.control-and-functional-verification.equipment.breaker.maintenance | Control and Functional Verification is specified for low-voltage power circuit breakers in maintenance testing at clause 7.6.1.2.B.11 of ANSI/NETA MTS-2023. Value: low-voltage power circuit breakers. |
Dielectric withstand
| Record | Statement |
|---|---|
| tests.dielectric-withstand.equipment.breaker.acceptance | Dielectric Withstand is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.B.11 of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
| tests.dielectric-withstand.equipment.breaker.maintenance | Dielectric Withstand is specified for oil and vacuum automatic circuit reclosers in maintenance testing at clause 7.24.1.B.10 of ANSI/NETA MTS-2023. Value: oil and vacuum automatic circuit reclosers. |
Dynamic Contact Resistance
| Record | Statement |
|---|---|
| tests.dynamic-contact-resistance.equipment.breaker.acceptance | Dynamic Contact Resistance is specified for medium-voltage and high-voltage oil circuit breakers in acceptance testing at clause 7.6.2.B.4 of ANSI/NETA ATS-2025. Value: medium-voltage and high-voltage oil circuit breakers. |
| tests.dynamic-contact-resistance.equipment.breaker.maintenance | Dynamic Contact Resistance is specified for medium-voltage and high-voltage oil circuit breakers in maintenance testing at clause 7.6.2.B of ANSI/NETA MTS-2023. Value: medium-voltage and high-voltage oil circuit breakers. |
| tests.dynamic-contact-resistance.governed-by.ansi-neta-ats | Dynamic Contact Resistance is addressed in ANSI/NETA ATS-2025. |
| tests.dynamic-contact-resistance.governed-by.ansi-neta-mts | Dynamic Contact Resistance is addressed in ANSI/NETA MTS-2023. |
| tests.dynamic-contact-resistance.title | The test method is named Dynamic Contact Resistance. Value: Dynamic Contact Resistance. |
Ground fault protection performance
| Record | Statement |
|---|---|
| tests.ground-fault-protection-performance.equipment.breaker.acceptance | Ground Fault Protection Performance is specified for low-voltage molded-case circuit breakers in acceptance testing at clause 7.6.1.1.1.B.5 of ANSI/NETA ATS-2025. Value: low-voltage molded-case circuit breakers. |
| tests.ground-fault-protection-performance.equipment.breaker.maintenance | Ground Fault Protection Performance is specified for low-voltage power circuit breakers in maintenance testing at clause 7.6.1.2.B.7 of ANSI/NETA MTS-2023. Value: low-voltage power circuit breakers. |
Insulation power factor dissipation factor
| Record | Statement |
|---|---|
| tests.insulation-power-factor-dissipation-factor.equipment.breaker.acceptance | Insulation Power Factor Dissipation Factor is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.B.7 of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
| tests.insulation-power-factor-dissipation-factor.equipment.breaker.maintenance | Insulation Power Factor Dissipation Factor is specified for oil and vacuum automatic circuit reclosers in maintenance testing at clause 7.24.1.B.7 of ANSI/NETA MTS-2023. Value: oil and vacuum automatic circuit reclosers. |
Insulation resistance
| Record | Statement |
|---|---|
| tests.insulation-resistance.equipment.breaker.acceptance | Insulation Resistance is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.B.2 of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
| tests.insulation-resistance.equipment.breaker.maintenance | Insulation Resistance is specified for oil and vacuum automatic circuit reclosers in maintenance testing at clause 7.24.1.B.2 of ANSI/NETA MTS-2023. Value: oil and vacuum automatic circuit reclosers. |
Primary Current Injection Trip Test
| Record | Statement |
|---|---|
| tests.primary-current-injection-trip-test.equipment.breaker.acceptance | Primary Current Injection Trip Test is specified for low-voltage molded-case circuit breakers in acceptance testing at clause 7.6.1.1.1.B.3 of ANSI/NETA ATS-2025. Value: low-voltage molded-case circuit breakers. |
| tests.primary-current-injection-trip-test.equipment.breaker.maintenance | Primary Current Injection Trip Test is specified for low-voltage power circuit breakers in maintenance testing at clause 7.6.1.2.B.5 of ANSI/NETA MTS-2023. Value: low-voltage power circuit breakers. |
| tests.primary-current-injection-trip-test.governed-by.ansi-neta-ats | Primary Current Injection Trip Test is addressed in ANSI/NETA ATS-2025. |
| tests.primary-current-injection-trip-test.governed-by.ansi-neta-mts | Primary Current Injection Trip Test is addressed in ANSI/NETA MTS-2023. |
| tests.primary-current-injection-trip-test.title | The test method is named Primary Current Injection Trip Test. Value: Primary Current Injection Trip Test. |
Resistor and coil resistance
| Record | Statement |
|---|---|
| tests.resistor-and-coil-resistance.equipment.breaker.acceptance | Resistor and Coil Resistance is specified for medium-voltage air circuit breakers in acceptance testing at clause 7.6.1.3.B.9 of ANSI/NETA ATS-2025. Value: medium-voltage air circuit breakers. |
| tests.resistor-and-coil-resistance.equipment.breaker.maintenance | Resistor and Coil Resistance is specified for medium-voltage air circuit breakers in maintenance testing at clause 7.6.1.3.B.10 of ANSI/NETA MTS-2023. Value: medium-voltage air circuit breakers. |
Trip and Close Coil Minimum Pickup
| Record | Statement |
|---|---|
| tests.trip-and-close-coil-minimum-pickup.equipment.breaker.acceptance | Trip and Close Coil Minimum Pickup is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.B.6 of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
| tests.trip-and-close-coil-minimum-pickup.equipment.breaker.maintenance | Trip and Close Coil Minimum Pickup is specified for oil and vacuum automatic circuit reclosers in maintenance testing at clause 7.24.1.B.6 of ANSI/NETA MTS-2023. Value: oil and vacuum automatic circuit reclosers. |
| tests.trip-and-close-coil-minimum-pickup.governed-by.ansi-neta-ats | Trip and Close Coil Minimum Pickup is addressed in ANSI/NETA ATS-2025. |
| tests.trip-and-close-coil-minimum-pickup.governed-by.ansi-neta-mts | Trip and Close Coil Minimum Pickup is addressed in ANSI/NETA MTS-2023. |
| tests.trip-and-close-coil-minimum-pickup.title | The test method is named Trip and Close Coil Minimum Pickup. Value: Trip and Close Coil Minimum Pickup. |
Trip Unit Secondary Injection
| Record | Statement |
|---|---|
| tests.trip-unit-secondary-injection.equipment.breaker.acceptance | Trip Unit Secondary Injection is specified for low-voltage molded-case circuit breakers in acceptance testing at clause 7.6.1.1.1.B.7 of ANSI/NETA ATS-2025. Value: low-voltage molded-case circuit breakers. |
| tests.trip-unit-secondary-injection.equipment.breaker.maintenance | Trip Unit Secondary Injection is specified for low-voltage power circuit breakers in maintenance testing at clause 7.6.1.2.B.9 of ANSI/NETA MTS-2023. Value: low-voltage power circuit breakers. |
| tests.trip-unit-secondary-injection.governed-by.ansi-neta-ats | Trip Unit Secondary Injection is addressed in ANSI/NETA ATS-2025. |
| tests.trip-unit-secondary-injection.governed-by.ansi-neta-mts | Trip Unit Secondary Injection is addressed in ANSI/NETA MTS-2023. |
| tests.trip-unit-secondary-injection.title | The test method is named Trip Unit Secondary Injection. Value: Trip Unit Secondary Injection. |
Vacuum interrupter integrity
| Record | Statement |
|---|---|
| tests.vacuum-interrupter-integrity.equipment.breaker.acceptance | Vacuum Interrupter Integrity is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.B.10 of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
| tests.vacuum-interrupter-integrity.equipment.breaker.maintenance | Vacuum Interrupter Integrity is specified for oil and vacuum automatic circuit reclosers in maintenance testing at clause 7.24.1.B.9 of ANSI/NETA MTS-2023. Value: oil and vacuum automatic circuit reclosers. |
Vacuum interrupter mac test
| Record | Statement |
|---|---|
| tests.vacuum-interrupter-mac-test.equipment.breaker.acceptance | Vacuum Interrupter MAC Test is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.B.9 of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
Visual and mechanical inspection
| Record | Statement |
|---|---|
| tests.visual-and-mechanical-inspection.equipment.breaker.acceptance | Visual and Mechanical Inspection is specified for oil and vacuum automatic circuit reclosers in acceptance testing at clause 7.24.1.A of ANSI/NETA ATS-2025. Value: oil and vacuum automatic circuit reclosers. |
| tests.visual-and-mechanical-inspection.equipment.breaker.maintenance | Visual and Mechanical Inspection is specified for oil and vacuum automatic circuit reclosers in maintenance testing at clause 7.24.1.A of ANSI/NETA MTS-2023. Value: oil and vacuum automatic circuit reclosers. |
Equipment classes
Low-voltage circuit breakers
| Record | Statement |
|---|---|
| equip.low-voltage-circuit-breakers.acc.contact-resistance | ANSI/NETA ATS-2025 calls for contact or pole resistance measurements on molded-case, insulated-case and low-voltage power circuit breakers at acceptance. |
| equip.low-voltage-circuit-breakers.acc.control-functional | ANSI/NETA ATS-2025 calls for verification of control and functional operation on insulated-case and low-voltage power circuit breakers at acceptance. |
| equip.low-voltage-circuit-breakers.acc.ground-fault | ANSI/NETA ATS-2025 calls for tests of ground-fault protection functions on molded-case, insulated-case and low-voltage power circuit breakers at acceptance. |
| equip.low-voltage-circuit-breakers.acc.insulation-resistance | ANSI/NETA ATS-2025 calls for insulation resistance tests on molded-case, insulated-case and low-voltage power circuit breakers at acceptance. |
| equip.low-voltage-circuit-breakers.acc.primary-injection | ANSI/NETA ATS-2025 calls for trip tests by primary current injection on molded-case, insulated-case and low-voltage power circuit breakers at acceptance. |
| equip.low-voltage-circuit-breakers.acc.secondary-injection | ANSI/NETA ATS-2025 calls for secondary injection tests of the trip unit on molded-case, insulated-case and low-voltage power circuit breakers at acceptance. |
| equip.low-voltage-circuit-breakers.acc.visual-mechanical | ANSI/NETA ATS-2025 opens its sections on molded-case, insulated-case and low-voltage power circuit breakers with visual and mechanical inspection. |
| equip.low-voltage-circuit-breakers.ats-sections | ANSI/NETA ATS-2025 treats low-voltage circuit breakers in separate sections for molded-case breakers (7.6.1.1.1), insulated-case breakers (7.6.1.1.2) and power circuit breakers (7.6.1.2). |
| equip.low-voltage-circuit-breakers.ats-tables | The ANSI/NETA ATS-2025 sections on low-voltage circuit breakers refer to Table 100.1 for insulation resistance, to Table 100.7 for inverse-time trip testing of molded-case breakers and to Table 100.8 for instantaneous trip tolerances. |
| equip.low-voltage-circuit-breakers.definition | A low-voltage circuit breaker is a circuit breaker built for low-voltage power circuits, a class that takes in molded-case, insulated-case and low-voltage power circuit breakers. |
| equip.low-voltage-circuit-breakers.mnt.coil-pickup | ANSI/NETA MTS-2023 calls for minimum pickup tests of trip and close coils on insulated-case and molded-case breakers in maintenance testing. |
| equip.low-voltage-circuit-breakers.mnt.contact-resistance | ANSI/NETA MTS-2023 calls for contact or pole resistance measurements on insulated-case, molded-case and low-voltage power circuit breakers in maintenance testing. |
| equip.low-voltage-circuit-breakers.mnt.control-functional | ANSI/NETA MTS-2023 calls for verification of control and functional operation on low-voltage power circuit breakers in maintenance testing. |
| equip.low-voltage-circuit-breakers.mnt.ground-fault | ANSI/NETA MTS-2023 calls for tests of ground-fault protection functions on insulated-case, molded-case and low-voltage power circuit breakers in maintenance testing. |
| equip.low-voltage-circuit-breakers.mnt.insulation-resistance | ANSI/NETA MTS-2023 calls for insulation resistance tests on insulated-case, molded-case and low-voltage power circuit breakers in maintenance testing. |
| equip.low-voltage-circuit-breakers.mnt.primary-injection | ANSI/NETA MTS-2023 calls for trip tests by primary current injection on insulated-case, molded-case and low-voltage power circuit breakers in maintenance testing. |
| equip.low-voltage-circuit-breakers.mnt.secondary-injection | ANSI/NETA MTS-2023 calls for secondary injection tests of the trip unit on insulated-case, molded-case and low-voltage power circuit breakers in maintenance testing. |
| equip.low-voltage-circuit-breakers.mnt.visual-mechanical | ANSI/NETA MTS-2023 opens its sections on insulated-case and molded-case breakers and on low-voltage power circuit breakers with visual and mechanical inspection. |
| equip.low-voltage-circuit-breakers.mts-sections | ANSI/NETA MTS-2023 treats insulated-case and molded-case breakers together in section 7.6.1.1 and low-voltage power circuit breakers in section 7.6.1.2. |
| equip.low-voltage-circuit-breakers.mts-tables | The ANSI/NETA MTS-2023 sections on low-voltage circuit breakers refer to Table 100.1 for insulation resistance, and the insulated-case and molded-case section also refers to Table 100.7 for inverse-time trip testing and to Table 100.8 for instantaneous trip tolerances. |
| equip.low-voltage-circuit-breakers.osha-definition | 29 CFR 1910.399 defines a circuit breaker as a device designed to open and close a circuit by nonautomatic means and to open the circuit automatically on a predetermined overcurrent without damage to itself when properly applied within its rating. |