Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance
Verified 2026-10-29 Confidence: High
Insulation Power Factor Dissipation Factor is specified for medium-voltage air circuit breakers in acceptance testing at clause 7.6.1.3.B.6 of ANSI/NETA ATS-2025. The clause calls for power-factor or dissipation-factor tests on each pole with the breaker open and each phase with the breaker closed.
Value: medium-voltage air circuit breakers
| Step | Item | Detail |
|---|---|---|
| Source | ANSI/NETA ATS-2025 | Licensed standard, clause 7.6.1.3.B.6 |
| Data record | tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance | Verified 2026-10-29 |
| Entry | Insulation Power Factor Dissipation Factor | No revisions |
- Subject
- Insulation Power Factor Dissipation Factor (Test methods)
- Kind
- Equipment fact
- Source
- ANSI/NETA ATS-2025, clause 7.6.1.3.B.6, Acceptance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA ATS-2025Publisher information page
- Also stated in
- FIST 4-7, section 6.1.10.2, page 46 (August 2023).
Read the reference passage
6.1.10.2 Insulation Test
"Power factor tests should be performed on each phase with the breaker in both the open and the closed position. Power factor tests should be performed on each bushing of oil-filled breakers. Use conductive straps and the hot collar procedure if bushings are not equipped with a power factor tap. The power factor of an insulation should remain constant with increasing test voltage if no discharges are present."
FIST 4-7, section 6.1.10.2, page 46, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- FIST 4-7, section 6.1.10.2, page 46 (August 2023).
History
| Date | Change |
|---|---|
| 2026-10-29 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance." Circuit Breaker Reference. 2026-10-29. https://www.circuitbreakerreference.com/data/tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance/.
Circuit Breaker Reference, Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance (Oct. 29, 2026), https://www.circuitbreakerreference.com/data/tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance/.
@misc{etr-data-tests-insulation-power-factor-dissipation-factor-equipment-breaker-mv-air-acceptance,
title = {Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance},
howpublished = {\url{https://www.circuitbreakerreference.com/data/tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance/}},
organization = {Circuit Breaker Reference},
publisher = {Circuit Breaker Reference},
year = {2026},
note = {last substantive change 2026-10-29}
}{{cite web |title=Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance |website=Circuit Breaker Reference |publisher=Circuit Breaker Reference |url=https://www.circuitbreakerreference.com/data/tests.insulation-power-factor-dissipation-factor.equipment.breaker-mv-air.acceptance/ |date=2026-10-29 |access-date=}}