Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance
Verified 2026-10-29 Confidence: High
Insulation Power Factor Dissipation Factor is specified for medium-voltage vacuum circuit breakers in acceptance testing at clause 7.6.3.B.7 of ANSI/NETA ATS-2025. The clause calls for power-factor or dissipation-factor tests on each pole with the breaker open and each phase with the breaker closed.
Value: medium-voltage vacuum circuit breakers
| Step | Item | Detail |
|---|---|---|
| Source | ANSI/NETA ATS-2025 | Licensed standard, clause 7.6.3.B.7 |
| Data record | tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance | Verified 2026-10-29 |
| Entry | Insulation Power Factor Dissipation Factor | No revisions |
- Subject
- Insulation Power Factor Dissipation Factor (Test methods)
- Kind
- Equipment fact
- Source
- ANSI/NETA ATS-2025, clause 7.6.3.B.7, Acceptance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA ATS-2025Publisher information page
- Also stated in
- FIST 3-16, section 6.3.2.2, page 48 (May 2024).
Read the reference passage
6.3.2.2 Power Factor or Watt-Loss Test
"The power factor test is specifically used to determine the condition of the surface insulation of the breaker, it will not give the condition of the vacuum interrupter. [...] This test is to be used with a baseline and the results trended over time."
FIST 3-16, section 6.3.2.2, page 48, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 6.3.2, page 46 (May 2024).
Read the reference passage
6.3.2 Insulation and Vacuum-integrity Test
"The hi-pot test is a pass/fail test and the power factor test will give a value which will usually allow trending. However, the test result of the power factor test is so low that the value obtained may not be able to show a meaningful trend. The power factor test will not give meaningful results pertaining to vacuum-integrity due to the circuit breakers high insulation values."
FIST 3-16, section 6.3.2, page 46, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 4-7, section 6.1.10.2, page 46 (August 2023).
Read the reference passage
6.1.10.2 Insulation Test
"Power factor tests should be performed on each phase with the breaker in both the open and the closed position. Power factor tests should be performed on each bushing of oil-filled breakers. Use conductive straps and the hot collar procedure if bushings are not equipped with a power factor tap. The power factor of an insulation should remain constant with increasing test voltage if no discharges are present."
FIST 4-7, section 6.1.10.2, page 46, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- FIST 3-16, section 6.3.2.2, page 48 (May 2024).
History
| Date | Change |
|---|---|
| 2026-10-29 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance." Circuit Breaker Reference. 2026-10-29. https://www.circuitbreakerreference.com/data/tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance/.
Circuit Breaker Reference, Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance (Oct. 29, 2026), https://www.circuitbreakerreference.com/data/tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance/.
@misc{etr-data-tests-insulation-power-factor-dissipation-factor-equipment-breaker-vacuum-acceptance,
title = {Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance},
howpublished = {\url{https://www.circuitbreakerreference.com/data/tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance/}},
organization = {Circuit Breaker Reference},
publisher = {Circuit Breaker Reference},
year = {2026},
note = {last substantive change 2026-10-29}
}{{cite web |title=Data record tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance |website=Circuit Breaker Reference |publisher=Circuit Breaker Reference |url=https://www.circuitbreakerreference.com/data/tests.insulation-power-factor-dissipation-factor.equipment.breaker-vacuum.acceptance/ |date=2026-10-29 |access-date=}}