Data record tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance
Verified 2026-10-29 Confidence: High
Vacuum Interrupter Integrity is specified for medium-voltage vacuum circuit breakers in maintenance testing at clause 7.6.3.B.7 of ANSI/NETA MTS-2023. The clause calls for a dielectric withstand voltage test across each open vacuum bottle, in strict accordance with the manufacturer's published data, as the integrity check of the interrupter.
Value: medium-voltage vacuum circuit breakers
| Step | Item | Detail |
|---|---|---|
| Source | ANSI/NETA MTS-2023 | Licensed standard, clause 7.6.3.B.7 |
| Data record | tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance | Verified 2026-10-29 |
| Entry | Vacuum Interrupter Integrity | No revisions |
- Subject
- Vacuum Interrupter Integrity (Test methods)
- Kind
- Equipment fact
- Source
- ANSI/NETA MTS-2023, clause 7.6.3.B.7, Maintenance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA MTS-2023Publisher information page
- Also stated in
- FIST 3-16, section 6.1.2, page 42 (May 2024).
Read the reference passage
6.1.2 Design and Operation
"Vacuum circuit breakers' primary points of weakness are the operating mechanism and the bellows which is attached to the moving contact on the vacuum bottle (Figure 6-2). Due to the number of operations of some of our generator breakers, the bellows can start to crack which can impact the vacuum of the breaker. The operating mechanisms for vacuum circuit breakers are typically spring operated. This also simplifies the maintenance of these breakers."
FIST 3-16, section 6.1.2, page 42, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 6.2.4, page 44 (May 2024).
Read the reference passage
6.2.4 Insulation and Vacuum-integrity Test
"A power factor or watt-loss test is not a test that will adequately test the insulation or the vacuum-integrity of a vacuum circuit breaker. A hi-pot test is required for this purpose."
FIST 3-16, section 6.2.4, page 44, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 6.3.2, page 46 (May 2024).
Read the reference passage
6.3.2 Insulation and Vacuum-integrity Test
"An insulation test will check for possible shorts to ground. A vacuum-integrity test will check the pressure of the vacuum bottle. These tests are critical to the continued safe operation of the circuit breaker."
FIST 3-16, section 6.3.2, page 46, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 6.1.2, page 42 (May 2024).
History
| Date | Change |
|---|---|
| 2026-10-29 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance." Circuit Breaker Reference. 2026-10-29. https://www.circuitbreakerreference.com/data/tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance/.
Circuit Breaker Reference, Data record tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance (Oct. 29, 2026), https://www.circuitbreakerreference.com/data/tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance/.
@misc{etr-data-tests-vacuum-interrupter-integrity-equipment-breaker-vacuum-maintenance,
title = {Data record tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance},
howpublished = {\url{https://www.circuitbreakerreference.com/data/tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance/}},
organization = {Circuit Breaker Reference},
publisher = {Circuit Breaker Reference},
year = {2026},
note = {last substantive change 2026-10-29}
}{{cite web |title=Data record tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance |website=Circuit Breaker Reference |publisher=Circuit Breaker Reference |url=https://www.circuitbreakerreference.com/data/tests.vacuum-interrupter-integrity.equipment.breaker-vacuum.maintenance/ |date=2026-10-29 |access-date=}}